Lighting circuit magnetic noise: an electrician’s troubleshooting guide

When a hearing loop buzzes with the lights on, the usual cause is net current in a lighting circuit: return current that doesn’t travel with the hot. This guide shows an electrician how to find it with a milliamp clamp, fix it, and prove the room is quiet enough.

By David Harmon, Founder & Principal ConsultantHow we write

Short answer

Lighting buzz in a hearing loop comes from net current: the hot and neutral of a circuit not carrying equal and opposite current along the same path. Find it by clamping the hot and neutral together; more than about 20 mA is a finding. Fix the current path first (borrowed neutrals, neutral-to-ground contact, split runs), then stop phase-cut dimming of LED drivers. The target is background noise of −47 dB(A) re 400 mA/m or quieter at the listening positions.

Not sure the buzz comes from the building at all? Start with the one test that tells you: if the hum is still there with the loop driver switched off, it’s the building, not the loop.

For licensed electricians

All line-voltage work in this guide is for a licensed electrician, under lockout/tagout and local code. Facilities staff: share this page with your electrician rather than opening boxes or fixtures yourself.

Why lighting buzz matters for a loop

For a hearing loop to sound clean, the room’s background magnetic noise has to be low. Buzz from a lighting circuit is one of the most common reasons a room isn’t.

  • How a loop works. The loop sends sound to hearing aids as a magnetic field, and the hearing aid’s telecoil picks it up. A telecoil also picks up every other magnetic field at audio frequencies, so buzz from building wiring goes straight into the listener’s ears.
  • The typical symptom. A loud, raspy buzz, strongest along a line in the floor or ceiling, that drops sharply when the room lights are switched off.
  • The target. IEC 60118-4 recommends background magnetic noise of about −47 dB(A) re 400 mA/m or quieter, and treats up to −32 dB(A) as acceptable in some rooms. Measure at the listening positions. Every 6 dB of reduction halves the magnetic field.
  • The fix. Find where the lighting current is flowing out of balance, correct it, and change the dimming if it’s part of the problem.

This is a wiring problem, not a hearing loop problem. Nothing on the loop side can filter it out.

The one idea: net current

A cable only radiates a magnetic field when the current going out on one path doesn’t come back on the same path. That imbalance is called net current, and finding it is the whole job.

The hot and neutral of a circuit carry equal and opposite current. When they lie side by side, their fields cancel within inches. When some of the return current takes a different route, the out-and-back paths form a large loop of current. That loop acts like a big antenna, and a hearing aid hears it across the room.

It takes very little. As a rough guide, about 20 mA of buzzy net current in a cable 5 ft (1.5 m) from a listener’s head is enough to miss the target. Ordinary load current doesn’t matter when the hot and neutral stay together.

Common causes of net current

  • Neutral-to-ground contact anywhere downstream: a pinched neutral in a box or fixture, or a neutral-ground bond at a subpanel. Part of the return current then comes back on the ground wire, conduit, steel or pipes.
  • Borrowed or swapped neutrals. This circuit’s neutral landed with another circuit, or two circuits share one neutral without being run together.
  • Multi-wire branch circuits where the hots and the shared neutral split into different cables or conduits along the way.
  • Switch loops and 3-way or 4-way wiring where the hot goes through the switch on one route and the neutral returns another way.
  • Fixture feeds daisy-chained so the hot goes one way around the room and the neutral another.

Why it sounds raspy, not just like hum

The sound of the buzz follows the shape of the current. Plain 60 Hz hum is mostly below what a telecoil hears. A sharp-edged current waveform has harmonics up into the kHz range, and those come through as a rasp.

  • A phase-cut dimmer switches on partway through each half-cycle. Feeding LED drivers, that makes a sharp current spike 120 times a second.
  • LED tube drivers rectify the line and charge a capacitor, so they draw current in narrow pulses at each voltage peak. That current is rich in odd harmonics, and cheap tubes are the worst. On a shared neutral, the 3rd harmonics add up instead of cancelling.

Fixing the waveform makes the buzz quieter. Fixing the current path makes the field go away. Do both, but the wiring comes first.

Tools

The key tool is a clamp meter that reads milliamps, because the net currents you’re hunting are tiny.

  • Leakage-current clamp (the kind used to trace GFCI trips), true-RMS, reading down to 1 mA. A standard clamp bottoms out around 0.1 A and will read zero on a real problem.
  • Standard true-RMS clamp meter for load currents.
  • Power-quality clamp with a harmonics or THD display (optional), to compare tubes and dimmers.
  • A multimeter, an insulation resistance tester, a circuit tracer and a non-contact voltage tester.
  • A field-strength meter or loop listener, so each change can be heard and measured as you go.

Step by step

Work in this order: identify what’s installed, test the dimmer, then hunt the net current with the clamp. Record readings on the readings sheet at the end.

  1. Set a baseline. Note the circuit number or numbers feeding the room lights. With the field meter at a listening spot, record the level with the lights on (dimmer at full) and off. The loud line may run in the floor (the ceiling of the space below) or in this room’s ceiling, so trace the circuit’s full route, including any run through the floor.
  2. Identify the dimmer. Pull it and record the make and model. The model number tells you which kind it is:
    • Phase-cut (incandescent or LED) dimmer: chops the line voltage itself. Most likely to cause the rasp with LED tubes.
    • Fluorescent dimmer for 3-wire dimming ballasts: has a switched hot plus a “dimmed hot” to the fixtures. Find out what that dimmed hot now feeds.
    • 0-10V dimmer: switches the line and sends a separate low-voltage control pair (usually purple and gray). Much quieter by design.
  3. Identify the tubes. Open a fixture and pull a tube. The label says which type it is:
    • Type A runs on the fluorescent ballast.
    • Type B has the ballast removed, with line voltage wired straight to the tube sockets.
    • Type C uses a separate remote LED driver.
    Note whether the ballast is still there, whether there’s a conversion label, and whether the tube says it’s dimmable.
  4. Sweep the slider. With the lights on, move the dimmer slowly from bottom to top while someone watches the field meter. If the noise level or tone changes with the slider, the dimmer is part of the problem. Record the level at full.
  5. Take the dimmer out, temporarily. De-energize, then replace the dimmer with a plain switch or a temporary connection. With a 3-wire fluorescent dimmer, work out how the tubes are fed before doing this. Measure again.
    • A big drop: the dimmer chopping into LED drivers is the main noise source.
    • Little change: the noise comes from the tube drivers plus the wiring.
    Carry on either way.
  6. Check net current at the panel, with the lights on at full. Use the leakage clamp.
    1. Clamp the circuit’s hot alone. This is the load current, for example 2.5 A.
    2. Clamp the circuit’s neutral alone. It should match the hot. If it reads clearly more or less, current is returning on another path, or another circuit’s current is on this neutral.
    3. Clamp the hot and neutral together in the jaw, nothing else. This is the net current. It should be a few mA. Over about 20 mA is a finding; hundreds of mA is a definite fault.
    4. Clamp the circuit’s ground wire alone, and the conduit if you can reach it. Both should read about zero. Current here means the neutral is touching ground somewhere downstream.
    5. On a multi-wire branch circuit, clamp all its hots plus the shared neutral together. They should net to about zero.
    6. Repeat with the lights off. Net current that disappears is the lighting. Net current that stays means another circuit shares this neutral, or other building current is involved. That can explain noise that remains with the lights off.
  7. Follow the net current along the run. At each box you can open (the switch box, junction boxes, each fixture whip), clamp the whole cable, or every conductor of the circuit in a conduit. Net current should be about zero everywhere. The spot where it appears or disappears brackets the fault.
    • At the switch box, clamp each cable entering. A switch loop with no neutral alongside the hot is a classic source.
    • The field meter helps: the loud line in the floor or ceiling follows the path the net current takes.
  8. Check the neutral directly, de-energized and locked out.
    • Lift the circuit’s neutral at the panel and test the insulation resistance from that neutral to ground. It should read open (megohms). A low reading means neutral-to-ground contact downstream; find it by splitting the circuit.
    • Confirm each neutral lands with its own hot. Turn off one circuit’s breaker: current on that circuit’s neutral should drop to zero. If it doesn’t, another circuit is using it.
    • At any subpanel, the neutral and ground bars must be separate, with no bonding screw or jumper.
  9. Check the fixtures. In fixtures converted to ballast bypass, check that line and neutral go to the sockets the tube label calls for. Check that no fixture gets its hot through one cable and its neutral through another. Cap or remove any leftover dimmed-hot conductors from the old dimming ballasts.
  10. Measure after each fix. Check the field level after every change, so you know which fix did what.

Fixes, in priority order

Fix the current path first. That removes the field no matter what the lights draw.

  1. Get the net current to zero. Correct swapped or borrowed neutrals and clear any neutral-to-ground contact. Keep every circuit’s hot and neutral (and all conductors of a multi-wire circuit) in the same cable or conduit along the whole run. Rewire switch loops and 3-way runs so the neutral travels with them.
  2. Stop chopping the line to LED tubes.
    • If they need dimming, use LED fixtures or retrofit kits with 0-10V dimming drivers and a matching 0-10V dimmer. The dimming then happens on the low-voltage control pair, not by chopping the power.
    • If they don’t need dimming, use a plain switch.
    • Either way, choose drivers or tubes with a power factor of at least 0.9 and THD of 20% or less (10% or less is better).
    • Don’t leave non-dimmable Type B tubes on a dimmer. Don’t leave Type A tubes on old dimming ballasts unless the tube maker lists that ballast.
  3. Measure again. If the room is still above −47 dB(A) with the lights off, there’s a second source. Use the same clamp method on the nearby circuits.

What won’t fix it

Shielding the cable, line filters and ferrites don’t stop a net current. Moving the hearing loop doesn’t help either, because the hearing aid hears the interference wherever the listener sits. Turning the loop up doesn’t remove the noise either.

Safety and code notes

All line-voltage work is for a licensed electrician, under lockout/tagout and local code. Most of the faults that cause net current are code issues anyway. The NEC references below are from the 2023 edition; check the edition your jurisdiction uses.

  • All conductors of a circuit together in the same raceway or cable: NEC 300.3(B).
  • No neutral-to-ground connection on the load side of the service disconnect: NEC 250.24(A)(5) and 250.142(B).
  • Multi-wire branch circuits: conductors grouped, with a common disconnect, NEC 210.4.
  • LED retrofits: non-dimmable ballast-bypass tubes on a dimmer are outside their listing. Converted fixtures should carry the labeling the retrofit maker requires.

Done when

The job is done when the lighting circuit’s net current is near zero and the room measures −47 dB(A) or quieter with the lights on.

  • Net current (hot and neutral clamped together) under 20 mA on each lighting circuit, at full brightness and at any dim setting
  • Ground wire and conduit current about zero
  • Dimming no longer chops the line feeding the LEDs (0-10V dimming or a plain switch)
  • Background noise at the listening positions of −47 dB(A) re 400 mA/m or quieter, lights on and off

Readings sheet

Print this page and fill in the sheet at the panel and along the run. Currents in amps, field level in dB.

Net current and field level readings, before and after the fix
ReadingWhereLights on, before fixLights off, before fixLights on, after fix
Hot alonePanel
Neutral alonePanel
Hot and neutral together (net)Panel
Ground wire alonePanel
ConduitPanel
Whole cable (net)Switch box
Whole cable (net)First fixture
Field level at listening spot (dB)Room

Questions about lighting noise

Why does a hearing loop buzz when the lights are on?

A telecoil picks up any magnetic field at audio frequencies, not only the loop’s. When a lighting circuit’s return current doesn’t travel with its hot, the two paths form a large loop that radiates a field, and LED drivers and phase-cut dimmers give that current sharp edges that come through as a rasp. The hearing loop itself is usually fine; the fix is in the wiring.

Will a filter, shielded cable or ferrite stop the buzz?

No. None of them stops a net current, and the field comes from the net current. Moving the hearing loop doesn’t help either, because the hearing aid picks up the interference wherever the listener sits. Get the net current to zero first, then deal with the dimming.

How much net current is too much?

As a rough guide, about 20 mA of buzzy net current in a cable 5 ft (1.5 m) from a listener’s head is enough to miss the −47 dB(A) target. A healthy circuit nets a few milliamps; hundreds of milliamps is a definite fault. Ordinary load current doesn’t matter when the hot and neutral stay together.

Want the room measured before and after?

We measure background magnetic noise across the seating with the loop off and on, so everyone can see where it’s worst and when it’s fixed. You’ll hear back from David within 2 business days.

  • Photos and a description first, free
  • We find the cause before anyone replaces anything
  • Any brand, any installer